The ultra-wide input voltage range can provide normal power supply even in remote areas with extremely harsh power environment, reducing the number of battery discharges and extending the battery life.
1-3kVA display panel can choose LCD display and LED display.
6kVA and above machines are equipped with LCD display panel as standard, which can clearly display the UPS operation status, load status, battery status, etc. on the panel, making it easier for users to read information and operate.
Advanced DSP digital control technology effectively improves product performance and system reliability.
The digitally controlled active power factor correction technology is used to make the input power factor as high as 0.99 or above, so as to avoid pollution to the power grid environment, reduce the UPS front-end power distribution costs, and reduce customer investment costs.
Automatic frequency recognition, adapting to 50Hz/60Hz power supply system, meeting global power supply system requirements.
The input voltage and frequency range is wide, which can better solve the generator configuration and control, and provide clean, safe and stable power supply for the load.
In case of abnormal mains power, the UPS can be started directly with the battery to meet emergency needs.
In the absence of battery, the UPS can be started directly with mains power, which can be used as a high-precision voltage-stabilized power supply.
It has ECO operation mode, which is highly efficient and energy-saving, and reduces user costs.
Model | HQ10G(L) | HQ20G(L) | HQ30G(L) | HQ60G(L) | HQ1110G(L) | |
Capacity | 1kVA | 2kVA | 3kVA | 6kVA | 10kVA | |
Enter | ||||||
Voltage range | 110~300Vac @50% load:160~280Vac @100% load | 110~300Vac @50% load; 176~300Vac @100% load | ||||
Frequency range | 40Hz~70 Hz | 46Hz~54 Hz @ 50Hz system; 56Hz~64 Hz @ 60Hz system | ||||
Power Factor | ≥0.99@100% load | |||||
Output | ||||||
Output voltage | 200/208/220/230/240Vac | 208/220/230/240Vac | ||||
Voltage accuracy | ±1% | |||||
Frequency range (synchronization range) | 47 Hz~ 53 Hz Or 57Hz ~63 Hz | 46Hz ~ 54Hz Or 56Hz~ 64 Hz | ||||
Frequency range (battery mode) | 50 Hz±0.25 Hz Or 60Hz±0.3 Hz | 50 Hz± 0.1 Hz Or 60Hz±0.1 Hz | ||||
Overload capacity | 105%~110%: 10 minutes; 110%~130%: 1 minute; >130%: 1 second | |||||
Power Factor | 0.8 | Standard 0.8 (optional 1) | ||||
Current peak ratio | 3:01 | |||||
Voltage waveform distortion | ≤3%@ 100% linear load; ≤6%@ 100% non-linear load | ≤3% @ 100% linear load; ≤5% @ 100% non-linear load | ||||
Switching time | Mains ↔ Battery | 0 ms | ||||
Inverter ↔ Bypass | <4ms | 0 ms | ||||
Efficiency | ||||||
Inverter mode | >88% | >89% | >90% | >92% | >93% | |
Battery | ||||||
Standard machine | Battery Model | 12V/7Ah | ||||
Number of batteries | 2 | 4 | 6 | Default 16 (16~20 adjustable) | ||
Charging Current | 1A | Default: 1 A; Maximum: 2A optional | ||||
Long extension machine | Charging voltage | 27.3Vdc±1% | 54.7 Vdc± 1% | 82.0 Vdc± 1% | 218.4 Vdc± 1% | |
Number of batteries | 2 | 4 | 6 | Default 16 (16~20 adjustable) | ||
Charging Current | 1A/2A/4A/6A | 1A/2A/4A/6A(6A only applies to 16-cell batteries) | ||||
Charging voltage | 27.3Vdc±1% | 54.7 Vdc± 1% | 82.0 Vdc± 1% | 218.4 Vdc± 1% | ||
Physical properties | ||||||
Standard machine | Dimensions Depth x Width x Height (mm) | 282 x145x220 | 397 x145x220 | 421 x 190 x318 | 369x190x688 | 442 x190x688 |
Net weight(kg) | 9.8 | 17 | 27.6 | 61 | 66 | |
Long extension machine | Dimensions Depth x Width x Height (mm) | 282 x145x220 | 397 x 145 x 220 | 369 x190x318 | 442 x190x318 | |
Net weight(kg) | 4.1 | 6.8 | 7.4 | 12 | 16 | |
Environmental conditions | ||||||
Operating Environment | Relative humidity 20-95% and temperature 0-40C (no condensation) | Relative humidity 0-95% and temperature 0-50C (no condensation) | ||||
Noise | <50dB(A)@ 1M | <55dB(A)@ 1M | ||||
Manager | ||||||
Intelligent RS-232 or USB | Supports Windows®2000/2003/XP/ista/2008/7/8, Linux, Unix and MAC | |||||
Optional SNMP | Supports power management via SNMP manager and web browser |