The latest IGBT rectification technology is used to achieve ultra-low input current harmonics, eliminate pollution to the power grid, reduce power factor compensation and harmonic control costs, and reduce cable losses.
The overall machine efficiency is as high as 95%, which greatly saves energy consumption and reduces operating costs.
When the quality of the mains power is high, the ECO economic mode can be used to power the load. The overall efficiency is as high as 99%, and the energy saving benefits are significant.
The inverter and PFC of the UPS adopt an advanced 32-bit high-speed digital signal processor DSP chip as the core control system to achieve faster data processing and signal control, greatly improving the performance indicators and reliability of the whole machine.
The ultra-wide AC input range can adapt to complex power grid environments.
Intelligent monitoring of computers and uninterruptible power supplies can be achieved through dry contact communication, and online monitoring can be achieved through SNMP, so that users can know the operating status of the equipment remotely.
The number of batteries can be adjusted from 30 to 44 to prevent battery failure from affecting system operation. Faulty batteries can be quickly removed to reduce maintenance time. For renovation projects, battery configuration is more flexible and investment costs are optimized.
When an emergency occurs, the UPS can be quickly shut down.
In case of abnormal mains power, the UPS can be started directly with the battery to meet emergency needs.
In the absence of battery, the UPS can be started directly with mains power, which can be used as a high-precision voltage-stabilized power supply.
The three-stage intelligent charging mode that is highly matched to the battery performance keeps the battery pack running healthily.
The battery secondary protection function effectively protects the battery and prevents the battery from being damaged by deep discharge of small current after the battery undervoltage protection.
√N+X parallel redundancy function
Supports multiple parallel networking, N+X power supply mode, and improves power supply reliability.
Parallel connection does not require additional parallel cards, and can be directly connected via parallel data cables.
Model | HP1000GRL | HP1500GRL | HP2000GRL | HP2500GRL | HP3000GRL | |
Capacity | 10 kVA | 15kVA | 20kVA | 25kVA | 30kVA | |
Main input | ||||||
Rated voltage | 380/400/415Vac (3 phases + N) | |||||
Voltage range | 304Vac~478Vac (line voltage) full load; 304Vac~228Vac (line voltage) load linearly derated from 100%~80% | |||||
Frequency range | 40Hz~ 70 Hz | |||||
Power Factor | ≥0.99@100% load; ≥0.98@50% load | |||||
Current harmonic components | THDi<3% (100% linear load); THDi<5% (100% non-linear load) | |||||
Inverter output | ||||||
Output voltage | 380/400/415Vac | |||||
Voltage accuracy | ±1%@balanced load; ±5%@unbalanced load | |||||
Voltage waveform distortion | THDu≤2%(100% linear load);THDu≤4%(non-linear load) | |||||
Power Factor | 1 | 0.9 | ||||
Frequency range (synchronization range) | Default ±2Hz; ±0.5Hz, ±1Hz, ±3Hz (adjustable) | |||||
Frequency range (battery mode) | 50 Hz ±0.1 Hz 或 60Hz±0.1 Hz | |||||
Overload capacity | <105%, long term; <110%, 60 minutes; 110~125% rated load, 10 minutes; >125~150% rated load, 1 minute; >150%, 200ms | |||||
Current peak ratio | 3:01 | |||||
Switching Time | Mains ↔ Battery | 0ms | ||||
Inverter ↔ Bypass | 0ms | |||||
Inverter ↔ ECO | <2ms | |||||
Efficiency | ||||||
Inverter mode | ≥95% | |||||
ECO Mode | ≥99% | |||||
Battery | ||||||
Battery Model | Varies depending on usage | |||||
Number of batteries | Default 32 knots; 30 ~44 (±15~±22) knots (adjustable) | |||||
Charging Current | Capacity*15%/N/12(N=±15~22) | |||||
Charging voltage | ±13.65Vdc*N± 1% (N=±15~22) | |||||
Physical properties | ||||||
Dimensions Depth x Width x Height (mm) | 735 x 482.6 x 130 (3U);580 x 482.6x 175 (4U) | |||||
Net weight(kg) | 37 | 39 | 42 | 44 | 46 | |
Environmental conditions | ||||||
Operating temperature | 0~40°C(Battery life will be shortened in environments >25°C) | |||||
Relative humidity | 0~95% no condensation | |||||
Altitude | No derating at 1000m, derating of 1% for every 100m above 1000m | |||||
Noise | ≤60dB (A)@ 1 M | |||||
Manage | ||||||
Intelligent RS-232/RS-485 | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC | |||||
Optional SNMP | Supports power management via SNMP manager and web browser |