The ultra-wide input voltage range can provide normal power supply even in remote areas with extremely harsh power environment, reducing the number of battery discharges and extending the battery life.
The LCD display panel clearly displays the operating conditions of the UPS, allowing users to keep abreast of changes in the operating status and application environment.
It adopts a 19-inch rack structure and can be installed in a standard cabinet, saving floor space and space; it is easy to install, use and maintain; and it is compatible with lithium iron battery backup.
The use of advanced DSP digital control technology effectively improves product performance and system reliability, and achieves higher power density integration and miniaturization.
The digitally controlled active power factor correction technology is used to make the input power factor as high as 0.99 or above to avoid pollution to the power grid environment, achieve energy saving and reduce system investment costs.
Automatic frequency recognition, adapting to 50Hz/60Hz power supply system, meeting global power supply system requirements.
The input voltage and frequency range is wide, which can better solve the generator configuration and control, and provide clean, safe and stable power supply for the load.
It has ECO operation mode, which is highly efficient and energy-saving, and reduces user costs.
Two input wiring methods can be set on site (380Vac and 220Vac optional), making installation more flexible.
With N+X parallel redundancy function.
In case of abnormal mains power, the UPS can be started directly with the battery to meet emergency use needs.
In the absence of battery, the UPS can be started directly with mains power and can be used as a high-precision voltage-stabilized power supply.
Model | HQ3110GR(L) | HQ3115GR(L) | HQ3120GR(L) | |
Capacity | 10kVA | 15kVA | 20kVA | |
Enter | ||||
Rated voltage | 380Vac (3 phase + N) | |||
Voltage range | 190 Vac ~520 Vac @50% load; 305 Vac~478 Vac @100% load | |||
Frequency range | 46Hz ~ 54 Hz @ 50Hz system; 56Hz ~ 64 Hz @ 60Hz system | |||
Power Factor | ≥0.99@100% load | |||
Output | ||||
Output voltage | 208/220/230/240Vac | |||
Voltage accuracy | ±1% | |||
Frequency range (synchronization range) | 46Hz~ 54 Hz Or 56Hz~ 64 Hz | |||
Frequency range (battery mode) | 50 Hz±0.1Hz Or 60Hz±0.1 Hz | |||
Power Factor | Standard 0.8 (optional 0.9) | |||
Current peak ratio | 3:01 | |||
Voltage waveform distortion | ≤2% @ 100% linear load: ≤5% @ 100% non-linear load | |||
Overload Capacity | Mains model | 105%~110%: 10 minutes; 110%~130%: 1 minute; >130%: 1 second | ||
Battery Model | 105%~110%: 30 seconds; 110%~130%: 10 seconds; >130%: 1 second | |||
Switching Time | Mains ↔ Battery | 0ms | ||
Inverter ↔ Bypass | 0ms | |||
Efficiency | ||||
Inverter mode | >90% | |||
Battery | ||||
Standard machine | Battery Model | 12V/7 Ah | ||
Number of batteries | Preset 16 knots (16~20 knots adjustable) | Preset 2x16 knots (16~20 knots adjustable) | ||
Charging Current | 1A±10% | 2A±10% | ||
Charging voltage | 218.4Vdc±1% | |||
Long extension machine | Number of batteries | Default 16 knots (16~20 knots adjustable) | ||
Charging Current | 4A±10% | |||
Charging voltage | 218.4Vdc±1% | |||
Physical properties | ||||
Standard machine | Dimensions Depth x Width x Height (mm) | UPS host: 668 x 482.6 x 133 [3U] | UPS host: 668 x 482.6 x266[6U] | |
Battery box: 580 x482.6 x 133[3U] | Battery box::580 x482.6 x 133[3U] x 2 pcs | |||
Net weight(kg) | UPS host: 22;Battery box:63 | UPS host: 45;Battery box:63 x2 pcs | ||
Long extension machine | Dimensions Depth x Width x Height (mm) | 668 x 482.6 x 133[3U] | 668 x 482.6 x 266[6U] | |
Net weight(kg) | 22 | 45 | ||
Environmental conditions | ||||
Operating Environment | Relative humidity 0-95% and temperature 0-40C (non-condensing) | |||
Noise | < 60 dB(A) @ 1M | < 65 dB(A) @ 1M | ||
Manage | ||||
Intelligent RS-232 or USB | Supports Windows®2000/2003/XP/Vista/2008/7/8, Linux and MAC | |||
Optional SNMP | Supports power management via SNMP managers and web browsers |