The ultra-wide input voltage range can provide normal power supply even in remote areas with extremely harsh power environment, reducing the number of battery discharges and extending the battery life.
The LCD display panel clearly displays the UPS operating status, load status, battery status, etc., allowing users to grasp the changes in the UPS operating status and application environment at any time.
When powered on and turned on, the UPS begins to self-check the key working circuits in order to detect problems in time and avoid any losses.
The digitally controlled active power factor correction technology is used to increase the input power factor to above 0.99, thus avoiding pollution to the power grid environment and reducing customer input costs.
Automatic frequency recognition, adapting to 50Hz/60Hz power supply system, meeting global power supply system requirements.
The input voltage and frequency range is wide, which can better solve the generator configuration and control, and provide clean, safe and stable power supply for the load.
Two input wiring methods can be set on site (380Vac and 220Vac optional), making installation more flexible.
With N+X parallel redundancy function.
Advanced parallel technology, high parallel reliability and less circulating current.
In case of abnormal mains power, the UPS can be started directly with the battery to meet emergency needs.
In the absence of battery, the UPS can be started directly with mains power, which can be used as a high-precision voltage-stabilized power supply.
It has ECO operation mode, which is highly efficient and energy-saving, and reduces user costs.
Model | HQ3110G(L) | HQ3115G(L) | HQ3120G(L) | |
Capacity | 10kVA | 15kVA | 20kVA | |
Enter | ||||
Rated voltage | 380Vac (3 phases + N) | |||
Voltage range | 190 Vac ~520 Vac @50% load; 305 Vac ~478 Vac @100% load | |||
Frequency range | 46Hz ~ 54 Hz @ 50Hz system; 56Hz ~ 64 Hz @ 60Hz system | |||
Power Factor | ≥0.99@100% load | |||
Output | ||||
Output voltage | 208/220/230/240Vac | |||
Voltage accuracy | ±1% | |||
Frequency range (synchronization range) | 46Hz~54 Hz Or 56Hz~ 64 Hz | |||
Frequency range (battery mode) | 50 Hz±0.1Hz Or 60Hz±0.1 Hz | |||
Power Factor | Standard 0.8 (optional 0.9) | |||
Current peak ratio | 3:01 | |||
Mains model | 105%~110%: 10 minutes; 110%~130%: 1 minute; >130%: 1 second | |||
Battery Mode | 105%~110%: 30 seconds; 110%~130%: 10 seconds; >130%: 1 second | |||
Voltage waveform distortion | ≤2% @ 100% linear load; ≤5% @ 100% non-linear load | |||
Switching Time | Mains ↔ Battery | 0ms | ||
Inverter ↔ Bypass | 0ms | |||
Efficiency | ||||
Inverter mode | 93% | 92% | ||
Standard machine | Number of batteries | Preset 16 knots (16~20 knots adjustable) | Preset 2x16 knots (16~20 knots adjustable) | |
Battery Time | 9 hours to reach 90% capacity | |||
Charging Current | 1A | 2A | ||
Charging voltage | 218.4Vdc±1% | |||
Long extension machine | Number of batteries | Default 16 knots (16~20 knots adjustable) | ||
Charging Current | 4A (optional 8A) | |||
Charging voltage | 218.4 Vdc±1% | |||
Physical properties | ||||
Standard machine | Dimensions Depth x Width x Height (mm) | 592 x 250 x 576 | 815 x 250 x826 | |
Net weight(kg) | 83 | 164 | ||
Long extension machine | Dimensions Depth x Width x Height (mm) | 592 x 250 x576 | ||
Net weight(kg) | 28 | 40 | ||
Environmental conditions | ||||
Operating Environment | Relative humidity 0-95% and temperature 0-40C (non-condensing) | |||
Noise | <60 dB(A) @ 1M | |||
Manage | ||||
Intelligent RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC | |||
Optional SNMP | Supports power management via SNMP manager and web browser |